LoRaWAN in detail

Wireless that works on site – because we measure it first.

Private LoRaWAN networks for pharma, chemicals and industry: measured on site, with two redundant gateways and mobile connectivity from two different carriers. No intervention in the corporate network or control system – and documented so it fits into a qualification.

868 MHz

licence-free SRD band in Europe

2 gateways

per building – every sensor received twice

2 carriers

SIM cards from different providers

< −100 dBm

reception of all nodes during the walkdown: GOOD

Wireless instead of cable

Measure where cables are expensive or impossible

LoRaWAN radio brings readings out of rooms where you don’t want to – or may not – run a cable. The sensor measures right at the point of interest, the gateway transmits independently of the plant network – no wall penetration, no cable tray, no change to the control system.

Why wireless – and not cable?

With cable

Control roomATEX zoneCleanroomControl centreExGMP Control system Ex proofRequalificationChange control 3 wall penetrations · cable tray · DCS change
  • Cable route through ATEX zones – ignition protection and Ex documentation
  • Penetrations into cleanrooms – approvals, requalification, possibly downtime
  • Interface in the control system – engineering and change control
  • Weeks to months of lead time

With wireless sensors

Control roomATEX zoneCleanroomControl centreExGMP Gateway 0 penetrations · no intervention · ready in days
  • Battery-powered sensor right at the measuring point
  • No penetration, no cable route, no change to the control system
  • Autonomous gateway – independent of the plant network
  • Ready to measure in days

Field record: 3 years of control-room monitoring data

3

years of continuous use

2

min interval

around the clock

788,400

payloads per sensor

3 × 365 × 24 h × 30/h

1.58

million readings

temperature + humidity

15

limit violations

reliably detected and reported

Every violation arrived as an email – before it could turn into a failure.

Where LoRaWAN works

Through walls and ceilingsThe 868 MHz signal penetrates masonry and concrete slabs – even across several floors.
Basements, shafts, technical roomsEven where Wi-Fi and mobile coverage are weak: control rooms, sub-distributions, utility shafts.
Sites and outdoor areasRanges from a few hundred metres indoors up to kilometres outdoors – several buildings on one network.
Cleanrooms and ATEX areasNo wall penetration, no cable tray through the zone. We check sensor suitability for each area per project.
Cold rooms and refrigerationProbe at the measuring point, radio module outside – seals and insulation stay untouched.
Without power or networkBattery-powered sensors with long runtimes, gateway with its own LTE link – no IT approval needed.

How it works

Five steps to a running wireless network

  1. 1

    Survey the building

    We measure radio coverage on site at every planned measuring point – signal strength and quality, even in basements and behind reinforced concrete.

    Walkdown

  2. 2

    Document everything

    Readings, gateway locations and antenna planning go into a report. It is the basis for installation – and for qualification in GMP.

    Radio report

  3. 3

    Order the starter kit

    The kit arrives pre-configured in a case: gateway, sensors and accessories, neatly packed and ready to go.

    In a case

  4. 4

    Plug in & place

    Plug the gateway in – the LTE link is up. Mount sensors by magnet, bracket or cable tie exactly where it’s critical.

    Plug & play

  5. 5

    Log in

    Sign in at monicore.one: live readings, set limits, activate email alerts. Done.

    Live data

More safety

One gateway to start – redundant when it matters

The number of gateways depends on the building and criticality. Every sensor transmits to all gateways in range; if one fails, the others take over automatically.

1gateway

Start & pilot

Ideal for getting started, one room or one floor.

2gateways

Redundant

Two gateways with SIM cards from two different carriers – our standard for critical areas.

3gateways

Large building

Several floors or long buildings: every measuring point is heard by at least two gateways.

4gateways

Campus & highest availability

Several buildings or a site – coverage with reserve, even while one gateway is serviced.

We deliver it all – from the starter kit in a case to a redundant network ready for qualification.

Request a site survey

Summary of our reports

What the reports say – at a glance.

Behind this page are experience, walkdown and measurement reports from several years of practice. The key results in brief:

Pilot at DSM since 2022

Experience report control-room monitoring

  • Trigger: temperature-related failures, room temperatures above +43 °C, rooms not accessible to operations
  • Two successful pilots (2022 and 2023), then continuous operation
  • Temperature and humidity every 2 minutes in five control rooms plus outdoor reference
  • Limit violations reported by e-mail, countermeasures taken before a failure

Technical and economic assessment

Experience report wireless monitoring

  • Typical weak points: split responsibility, missing alarm chain, operators without access
  • Alarm e-mail with location, value, duration, max/min and 24 h trend; pre- and main alarm
  • Review of a silent air-conditioner failure: moment visible in the trend to the minute
  • Service package from walkdown via FAT/SAT to DQ/IQ/OQ/PQ and training

On-site measurement, network planning

Walkdown report

  • Reference measurement with mobile gateway on a tripod and test node at every point
  • LoRaWAN result: all nodes better than −100 dBm = good
  • Mobile network without external antenna only medium – hence external LTE antenna
  • Mounting rules for nodes, gateways and antennas; coverage checked near the border

Basics of radio planning

LoRa guide

  • dB, RSSI, SNR and preamble explained
  • Link budget example with 151 dB
  • Attenuation of typical building materials, Fresnel zone, spreading factor and ADR
  • System components: sensor, gateway, server, application

Own measurement per radio packet

Current measurement & battery life

  • 13.8 mAs (SF7) to 81.7 mAs (SF12) per transmission at 14 dBm
  • Calculated ≈ 18 years at SF7, ≈ 3 years at SF12 (D cell, every 2 min)
  • M1 Node therefore designed for up to 10 years
  • Conclusion: good gateway position = low SF = long life

Walkdowns and reports via QR code

Scan & Forget – QR concept

  • Identify devices uniquely by QR code
  • Document safety rounds (e.g. emergency showers) via QR
  • Fault and maintenance reports straight to the responsible team
  • Inspection records retrievable instead of paper lists

Sketches based on photos from pilot and starter kit

M1MoniCoreOneStarter Kit M1MoniCoreOneM1 Gateway · LTE LTE-AntenneLoRa-Rundstrahler 868 MHz
Sketch
Starter kit: gateway with LoRa ground-plane and LTE antenna on mounting plate
M1MoniCoreOneM1 Gateway · LTE M1MoniCoreOneM1 NodeM1MoniCoreOneM1 Node
Sketch
Starter kit with gateway and two wireless sensors with PT100 probe
M1MoniCoreOneM1 Node Thermostat (vorhanden) PT100 am Kältekreis
Sketch
Sensor with PT100 probe on a refrigeration unit
M1MoniCoreOneM1 Node Montage ohne Bohren: Halter an Profilschiene
Sketch
Mounting on a strut channel in a technical room
M1MoniCoreOneM1 Node Antenne 868 MHzT/rF-Fühler · PT100
Sketch
M1 Node with humidity probe and PT100 cable
Symbolic illustration based on photos from our pilot projects. Series design may differ.

Basics

LoRaWAN explained in five minutes.

LoRaWAN (Long Range Wide Area Network) is an open radio standard of the LoRa Alliance for sensors that send small amounts of data over long distances – battery-powered, for years. It is ideal for industrial sites: signals pass through walls and ceilings, and sensors need neither cables nor network sockets.

Star topology

Each sensor (node) transmits directly to the gateways in range. If one node fails, the others are unaffected – there is no mesh that needs to rebuild.

Licence-free, but regulated

Transmission takes place in the 863–870 MHz SRD band. Each device may transmit at most 1 % of the time (duty cycle) – 36 seconds per hour – at max. 25 mW.

Encrypted

Every message is end-to-end encrypted with AES-128. Each node gets its own keys; without them nobody can read or inject data.

Very low transmit power

Typically 10 mW, max. 25 mW – Wi-Fi transmits at 100 mW to 1 W, mobile networks above 1 W. And a node only transmits for fractions of a second, e.g. every 2 minutes.

Spreading factor: range versus airtime

The spreading factor (SF7 to SF12) “stretches” the radio signal. More stretching means more range – but longer airtime, more battery use and fewer messages allowed per hour. The goal of good planning: the lowest possible SF, i.e. placing gateways so that sensors can use SF7.

Guide values for a short payload at 125 kHz bandwidth. Theoretically up to 5 km (SF7) or 16 km (SF12) – much less in reinforced-concrete buildings. That is exactly why we measure on site.

Choose SF

Airtime per message
max. messages per hour (1 % duty cycle)
Range (relative)
calculated battery life (D cell 19 Ah, every 2 min, 14 dBm)

Life from our own current measurement per radio packet (13.8 mAs at SF7 to 81.7 mAs at SF12) plus sleep current – without self-discharge and temperature effects. That is why we design for 10 years and place gateways so that SF7 is enough.

Radio planning in detail

Why we calculate – and then measure anyway.

A radio network can be described by three properties: range, data rate and energy consumption. In practice, at most two can be optimised. LoRaWAN goes for range and low energy – with a small data rate. Exactly right for readings every few minutes.

Decibels in one sentence

  • 3 dB more = double the power, 10 dB = ten times, 20 dB = a hundred times.
  • Double the distance = 6 dB more free-space loss.
  • dB simply add up: 14 dBm transmit power − 2 dB cable + 2 dBi antenna = 14 dBm radiated.

Example link budget

Transmit power14 dBm
Bandwidth 125 kHz10·log(125,000) = 51 dB
Receiver noise figure6 dB
SNR limit at SF12−20 dB
Sensitivity−174 + 51 + 6 − 20 = −137 dBm
Link budget14 − (−137) = 151 dB

151 dB covers very long distances in open terrain. On site, walls, slabs and metal eat up this margin – that is why measuring on site matters.

Fresnel zone

!

Even with line of sight, the space around the direct line matters: an obstacle in the first Fresnel zone – a pipe bridge, a roof structure – noticeably lowers the level. So gateways go high and free.

What walls cost: typical attenuation at 900 MHz

  • Glass 6 mm0.8 dB
  • Glass 13 mm2 dB
  • Wood 76 mm2.8 dB
  • Brick 89 mm3.5 dB
  • Brick 178 mm5 dB
  • Brick 267 mm7 dB
  • Concrete 102 mm12 dB
  • Stone wall 203 mm12 dB
  • Brick-concrete 192 mm14 dB
  • Stone wall 406 mm17 dB
  • Concrete 203 mm23 dB
  • Reinforced concrete 89 mm27 dB
  • Stone wall 610 mm28 dB
  • Concrete 305 mm35 dB

Guide values. Reinforced concrete, metal containers and tank farms can attenuate much more – the walkdown measures the real value.

Adaptive data rate (ADR)

The network automatically sets each sensor’s spreading factor: well-received sensors transmit faster and save battery. Good gateway positions are the prerequisite.

Our planning rules

  • The link budget sets the maximum range – attenuation is subtracted from it.
  • Reflections from ground and obstacles affect the level; sensors usually sit close to the ground.
  • Obstacles in the first Fresnel zone shorten the range.
  • Sensitivity depends on SNR, noise figure and bandwidth.
  • In the EU: max. 14 dBm transmit power (ERP 25 mW) and 1 % airtime in the 868 MHz band.

Why at all?

Critical infrastructure often runs blind.

Control, server and infrastructure rooms house PLCs, power supplies, switches and SIL cards – the basis of all production. Yet they are rarely measured. This is what we have seen in many plants:

Split responsibility

Air conditioning, control cabinets and access often belong to different departments. When cooling fails, nobody feels directly responsible.

No fast alarm chain

Maintenance by external contractors, unclear reporting paths – hours or days pass before the right person is on site.

Undefined states

Overheated electronics fail sporadically – from single signal channels to the entire control system. SIL cards can no longer be relied upon.

Alarm flood instead of information

Central collective alarms without clear assignment get acknowledged and forgotten. Room temperature is not a process alarm and does not belong to the operator.

No access, no visibility

Shift staff are usually not allowed into control or server rooms. A problem is only noticed when the control system HMI fails.

Ageing through heat

Permanently high temperature and humidity accelerate component ageing and promote condensation – long before anything fails.

Pilot cases from practice

Three rooms, three causes – reported in time every time.

From our pilot projects in control rooms (since 2022). Each case shows a different radio challenge – and why measuring on site is decisive.

Gateway building Tank farm Control room ≈ 400 m · no line of sight

Pilot 1 · Distance

Situation
Room temperatures above +43 °C, sporadic failures of two fixed air conditioners and unmonitored mobile units. The room was not accessible to operations.
Radio challenge
Radio path approx. 400 m line of sight without visibility – across several buildings and a tank farm with metal and reinforced concrete. WirelessHART or Wi-Fi would not have managed it.
Result
Several overtemperatures reliably alarmed, fault service called directly, production losses and component damage avoided.
Metal container = Faraday cage

Pilot 2 · Metal enclosure

Situation
A new air conditioner was switched off manually during a winter inspection – and not switched on again. In spring the temperature rose sharply.
Radio challenge
Several closed rooms made entirely of metal containers – a Faraday cage. Here the problem was not distance but the attenuation of the enclosure.
Result
Overtemperature alarmed in spring before another communication module failed; 24/7 monitoring since then without additional staff.
30 °C cooling off Alarm ✉

Pilot 3 · Silent failure

Situation
An air conditioner stopped cooling but kept running without a fault message. Nothing was visible on site.
Radio challenge
A thermostat would only have delivered a switching contact – no trend, no analysis, possibly acknowledged in the control system.
Result
Temperature rise detected and reported by e-mail; the trend shows the moment cooling failed to the minute.

What every alarm e-mail contains

  • Where: plant, room, sensor with equipment tag
  • What: current value and exceeded limit
  • When: start of the deviation and return to the target range
  • How long and how far: duration plus highest/lowest value
  • Trend: average, maximum and minimum of the last 24 h
  • Levels: pre-alarm (warning) and main alarm to defined recipients

What a project includes

  • On-site walkdown with individual signal measurement of all points
  • Hardware: nodes, gateways, antennas, SIM cards
  • Dashboard in MoniCore.one with alerting
  • FAT (hardware and software) at egatti, SAT at the customer
  • Qualification documents based on the walkdown report
  • Commissioning, final report and training
  • Optional spare parts (nodes/gateway) and extensions
  • Support throughout the entire term

Approach in pharma

From walkdown to qualification – seven steps.

In regulated environments it is not enough that it works – it must demonstrably work. Many of our FAT and SAT checks are exactly the activities required in installation and operational qualification (IQ/OQ).

  1. 01

    Requirements & use cases

    Which rooms and plants are business-critical? Which measurands, limits, pre-alarms and main alarms? Who is informed when? Is the measuring point GMP-relevant, ATEX-relevant, is a UPS needed?

    URS / specification

  2. 02

    Walkdown on site

    Site survey with building plans: measuring points, node and gateway positions and 230 V connections are defined. Reference measurement with a mobile gateway on a tripod and a test node – at every measuring point. Plus mobile network measurement per carrier. Photos and equipment tagging according to customer standards.

    Walkdown report = basis of the DQ

  3. 03

    Network planning

    Gateway locations and antenna orientation according to the building structure, at least two gateways per building, SIM cards from different carriers, power supplies on separate circuits. Each node should be received by both gateways.

    Network plan, device list

  4. 04

    FAT at egatti

    The entire network is commissioned at our premises first: gateways, nodes, keys, limits, alarm recipients and dashboard. Only after a passed factory acceptance test do we go to the customer.

    FAT protocol

  5. 05

    Installation & SAT

    Installation according to specifications, individual signal measurement of each node at both gateways, test of limit alarms, gateway redundancy (one gateway is deliberately switched off) and the e-mail alarm chain.

    SAT protocol

  6. 06

    Qualification (if GMP)

    DQ via the walkdown report, IQ for installation and documentation, OQ for function within limits, PQ under real conditions – e.g. limit alarms, gateway redundancy, alarming and optional audit trail.

    DQ · IQ · OQ · PQ

  7. 07

    Operation & support

    Watchdog (“last seen”) per node, monitoring of all gateways, battery voltage measured under load once a day, remote configuration and updates, staff training, final report.

    Final report, training

Nodes

How we bring sensors into a pharma plant.

A node is a battery-powered wireless sensor directly at the measuring point. It measures, encrypts and transmits – and needs no cable tray, no wall penetration and no interface in the control system. This keeps process alarms and infrastructure monitoring cleanly separated.

  • Measuring point and equipment tag are defined together during the walkdown – the tag appears on the device, in the dashboard and in every alarm e-mail.
  • Mounting height from approx. 1.5 m for good range, but max. 1.80 m – so service is possible without a ladder.
  • Antenna approx. 20 cm from the wall, free of metal housings and reinforced concrete directly at the device; use openings such as windows or doors.
  • Fixing with magnet, cable tie or screw – without drilling into cleanroom envelopes; temporary measurements are possible at any time.
  • Each node is checked individually: signal strength (RSSI) and signal-to-noise ratio (SNR) at both gateways, documented in the SAT.
  • For especially critical points: two independent sensors at the same position (sensor redundancy).
  • Monitored in operation: last message (watchdog), battery voltage under load, signal strength, packet counter and error status.

Mounting dimensions from our walkdown guidelines

Ceiling Floor Wall LoRa antenna LTE antenna Gateway Node ≥ 2.20 m ≥ 2.00 m ≤ 1.80 m ≥ 50 cm ≥ 50 cm Antennas ≥ 50 cm from wall and ceiling · devices reachable without aids
mobile gateway test node live readingRSSI −56 dBmSNR 10,3 dB · SF7

Walkdown: mobile gateway on a tripod, test node at the planned measuring point

Gateway design & resilience

Two gateways, two carriers, two circuits.

The gateway is the heart of the network – so with us there is never just one. Per building we plan at least two independent gateways, each covering the entire building. If one fails or is serviced, the other takes over – without losing a single reading.

MoniCore.one Mobile A Mobile B Gateway 1SIM network A Gateway 2SIM network B Circuit 1 Circuit 2 ✓ 0 readings lost
  • Normal operation – both paths active
  • Network A down – data via network B
  • Circuit 2 off – gateway 1 takes over

Two independent gateways

Every node is received by both. We show this in the walkdown with measurements at both gateways – not with an assumption.

SIM cards from different carriers

Each gateway has its own LTE SIM from a different provider. If one mobile network fails, data flows through the other.

Separate circuits

The power supplies are on different circuits – optionally on the UPS, so measuring and alarming continue during a power failure.

No intervention in the corporate network

The gateways transmit via mobile network. No firewall rules, no VLAN and no interface in the control system are needed.

External antennas, mounted indoors

LoRa and LTE antennas external to the gateway, installed inside the building – so no lightning protection assessment is needed.

Monitored and remotely maintainable

All gateways are visible in the dashboard; a failure is reported. Settings and updates are possible remotely – important for hard-to-access rooms.

Orienting the antenna correctly

  • One level

    Antenna vertical, gateway as central as possible in the area.

  • Several floors

    Gateway in the middle of the building, antenna horizontal – the “donut” pattern radiates up and down.

  • From outside

    Gateway outside, antenna vertical: windows attenuate less than reinforced-concrete slabs.

  • Border region

    In the DE/CH/FR tri-border area, Swiss cell towers can interfere. We check coverage per carrier in advance.

Measurements, not assumptions

Excerpt from a real walkdown report.

This is what the result of an on-site measurement looks like (anonymised). Each sensor is measured at both gateways – and where one gateway is further away, the other is close. That is intentional.

Measuring pointGateway 1Gateway 2Rating
Control room 1−56 dBm · SNR 10.25 dB−77 dBm · SNR 9.75 dBgood
Control room 2−79 dBm · SNR 10.25 dB−56 dBm · SNR 9.0 dBgood
Mobile network at gateway locationRSRP −101 dBm · RSRQ −13.5 dB · SINR 4 dBmedium – measured without external antenna → external LTE antenna planned

RSSI

Received signal strength in dBm. The closer to 0, the better. Walkdown rule: all nodes better than −100 dBm = GOOD.

SNR

Signal-to-noise ratio in dB. Positive values are very good; LoRa can even decode signals below the noise floor.

RSRP / RSRQ / SINR

Mobile network indicators at the gateway. They decide whether an external LTE antenna or a different carrier is needed.

Demonstrator 2022–2025

DataDOT ONE – three years of demo in continuous operation.

Note

The DataDOT ONE was our demonstrator in the pilot project. It ran in continuous operation for three years and is not a current product. The platform and solution are called MoniCore.one; the experience from the demo flows into our own sensor family MoniCore M1+.

What the demo showed in real operation – in control rooms of a production building, measuring every 2 minutes:

  • Temperature and humidity at the measuring point, plus an external PT100 probe (4-wire) with wire-break monitoring
  • Optional autonomous local alarm with bright LED and buzzer (> 100 dB) – works even if the radio link or gateway fails
  • Battery voltage measured under load once a day – the real battery condition, not just the open-circuit voltage
  • Status values online: signal strength, SNR, packet counter, internal temperature/humidity, error status; configuration by remote command
  • Transmitting at SF7 – thanks to good gateway positions short airtime and long battery life
To the DSM reference
M1MoniCoreOne Antenna 868 MHz Temperature /humidity PT100, 4-wire LED + buzzer > 100 dB Battery, checked under load daily

DataDOT ONE – demo sensor (sketch)

Control cabinets Air conditioner Sensor ≤ 1,80 m

Installation in a control room (sketch)

Node TM-001last seen 1 minBattery3.68 VRSSI−91 dBmSNR10.25 dBPackets74,849Temperature19.5 °CHumidity42 %PT100OKErrors0

Node status view (sketch)

FAQ on LoRaWAN on site

Do we need our corporate network or IT?

No. The gateways transmit via mobile network (LTE) directly to MoniCore.one. There is no implementation in the corporate network and no interface in the control system. Connection to your own servers is possible on request.

What happens if a gateway or mobile network fails?

Each sensor is received by two gateways that use SIM cards from different carriers and are connected to separate circuits. If one path fails, data flows through the other. The failure itself is reported in the dashboard.

Is radio exposure an issue?

LoRaWAN nodes typically transmit at 10 mW (max. 25 mW) and only for fractions of a second – at most 1 % of the time, in practice usually below 0.03 %. That is orders of magnitude less than Wi-Fi or a mobile phone.

How long do the batteries last?

It depends on the transmit interval and spreading factor. With good gateway planning (low SF), several years are common. Battery voltage is monitored, so replacement can be planned.

Can the system be qualified?

Yes. Walkdown report (DQ), FAT and SAT provide the basis for IQ and OQ; the PQ tests e.g. limit alarms, gateway redundancy and the alarm chain. We agree the scope with your quality assurance.

Does it work in ATEX zones?

Ex areas require approved devices. Whether and how a measuring point in a zone can be implemented is checked in the project – often it is enough to place the sensor outside and route a probe inside.

Shall we survey your site?

A walkdown with a mobile gateway shows within a few hours how many gateways you need and where – with measurements for every point.

Request a walkdown